2026/331 21.4.2026
COMMISSION DELEGATED REGULATION(EU) 2026/331
of 13 February 2026
supplementing Regulation (EU) 2024/3110 of the European Parliament and of the Council by
determining classes of performance in relation to the essential characteristic reaction to fire
(Text with EEA relevance)
THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Having regard to Regulation (EU) 2024/3110 of the European Parliament and of the Council of 27 November 2024 laying
down harmonised rules for the marketing of construction products and repealing Regulation (EU) No 305/2011(1), and in
particular Article 5(5), third subparagraph thereof,
Whereas:
(1) In order to enable manufacturers to declare sufficiently detailed classes of performance of products within the
harmonised zone established pursuant to Article 11 of Regulation (EU) 2024/3110, it is necessary to establish
classes of performance that are aligned to the latest technological and market developments.
(2) Classes of performance in relation to the essential characteristic reaction to fire were established by Commission
Delegated Regulation (EU) 2016/364(2) on the basis of Regulation (EU) No 305/2011 of the European Parliament
and of the Council(3). However, those classes of performance are not applicable under Regulation (EU) 2024/3110.
Therefore, in order to keep the continuity of the system, the CPR Acquis Expert Group advised the Commission to
establish the same classes of performance set out by Delegated Regulation (EU) 2016/364.
(3) The Commission should therefore determine the classes of performance to be used for the declaration of the essential
characteristic reaction to fire,
HAS ADOPTED THIS REGULATION:
Article 1
The classes of performance in relation to the essential characteristic reaction to fire of products shall be those set out in the
Annex.
(1) OJ L, 2024/3110, 18.12.2024, ELI: http://data.europa.eu/eli/reg/2024/3110/oj.
(2) Commission Delegated Regulation (EU) 2016/364 of 1 July 2015 on the classification of the reaction to fire performance of
construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council (OJ L 68, 15.3.2016,
p. 4, ELI: http://data.europa.eu/eli/reg_del/2016/364/oj).
(3) Regulation (EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 laying down harmonised conditions
for the marketing of construction products and repealing Council Directive 89/106/EEC (OJ L 88, 4.4.2011, p. 5, ELI: http://data.
europa.eu/eli/reg/2011/305/oj).
ELI: http://data.europa.eu/eli/reg_del/2026/331/oj 1/10EN
OJ L, 21.4.2026
Article 2
This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the
European Union.
This Regulation shall be binding in its entirety and directly applicable in all Member States.
Done at Brussels, 13 February 2026.
For the Commission
The President
Ursula VON DER LEYEN
2/10 ELI: http://data.europa.eu/eli/reg_del/2026/331/ojEN
OJ L, 21.4.2026
ANNEX
A. SYMBOLS
For the purposes of this Annex, the following symbols apply:
For all classes
ΔΤ temperature rise
Δm mass loss
t duration of flaming
f
PCS gross calorific potential
LFS lateral flame spread
SMOGRA smoke growth rate
For all classes except for classes related to electric cables
FIGRA fire growth rate
THR total heat release
TSP total smoke production
Fs flame spread
For classes related to electric cables only
HRR , kW heat release rate averaged by a 30-s sliding average
sm30
SPR , m2/s smoke production rate averaged by a 60-s sliding average
sm60
Peak HRR, kW maximum of HRR between test start and end of test, excluded contribution from
sm30
ignition source
Peak SPR, m2/s maximum of SPR between test start and end of test
sm60
THR , MJ total heat release (HRR ) from test start until end of test, excluded contribution from
1200 sm30
ignition source
TSP , m2 total smoke production (HRR ) from test start until end of test
1200 sm60
FIGRA, W/s fire growth rate index defined as the highest value of the quotient between HRR
sm30
excluding the contribution of ignition source and time. Threshold values HRR = 3 kW
sm30
and THR = 0,4 MJ
FS flame spread (damaged length)
H flame spread
B. DEFINITIONS
For the purposes of this Annex the following definitions apply:
(1) ‘material’ means a single basic substance or uniformly dispersed mixture of substances;
(2) ‘homogeneous product’ means a product consisting of a single material, having uniform density and
composition throughout the product;
(3) ‘non-homogeneous product’ means a product that does not satisfy the requirements of a homogeneous product
and that is composed of one or more components, substantial and/or non-substantial;
(4) ‘substantial component’ means a material that constitutes a significant part of a non-homogeneous product. A
layer with a mass per unit area ≥ 1,0 kg/m2 or a thickness ≥ 1,0 mm is considered to be a substantial
component;
ELI: http://data.europa.eu/eli/reg_del/2026/331/oj 3/10EN
OJ L, 21.4.2026
(5) ‘non-substantial component’ means a material that does not constitute a significant part of a non-
homogeneous product. A layer with a mass per unit area < 1,0 kg/m2and a thickness < 1,0 mm is considered
to be a non- substantial component. Two or more non-substantial layers that are adjacent to each other, where
there are no substantial components in between the layers, are considered as one non-substantial component
and are classified in accordance with the criteria for a layer that is a non-substantial component;
(6) ‘internal non-substantial component’ means a non-substantial component that is covered on both sides by at
least one substantial component;
(7) ‘external non-substantial component’ means a non-substantial component that is not covered on one side by a
substantial component.
C. CLASSES OF PERFORMANCE IN RELATION TO THE ESSENTIAL CHARACTERISTIC REACTION TO FIRE OF PRODUCTS
General
The relevant definitions, tests and performance criteria are fully described or referenced in the relevant harmonised
technical specifications, European assessment documents, European reaction to fire classification standards and
European testing standards.
1. Products excluding floorings, linear pipe thermal insulation products, and electric cables
Table 1
Class Test method(s) Classification criteria Additional classification
A1 Non-combustibility ΔΤ ≤ 30 °C;
test(1); and
and Δm ≤ 50 %;
and
t = 0 (that is to say, no sustained
f
flaming).
Heat of combustion test PCS ≤ 2,0 MJkg-1(1);
and
PCS ≤ 2,0 MJkg-1(2)(3);
and
PCS ≤ 1,4 MJm-2(4);
and
PCS ≤ 2,0 MJkg-1(5).
A2 Non-combustibility ΔΤ ≤ 50 °C;
test(1); and
or Δm ≤ 50 %;
and
t ≤ 20 s.
f
Heat of combustion PCS ≤ 3,0 MJkg-1(1);
test; and
and PCS ≤ 4,0 MJm-2(2);
and
PCS ≤ 4,0 MJm-2(4);
and
PCS ≤ 3,0 MJkg-1(5).
Single burning item FIGRA ≤ 120 Ws-1; Smoke production(6);
0,2MJ
test). and and
LFS < edge of specimen; Flaming droplets/particles(7).
and
THR ≤ 7,5 MJ.
600s
4/10 ELI: http://data.europa.eu/eli/reg_del/2026/331/ojEN
OJ L, 21.4.2026
Class Test method(s) Classification criteria Additional classification
B Single burning item FIGRA ≤ 120 Ws-1; Smoke production(6);
0,2MJ
test; and and
and LFS < edge of specimen; Flaming droplets/particles(7).
and
THR ≤ 7,5 MJ.
600s
Ignitability test(8): Fs ≤ 150 mm within 60 s.
Exposure = 30 s.
C Single burning item FIGRA ≤ 250 Ws-1; Smoke production(6);
0,4MJ
test; and and
and LFS < edge of specimen; Flaming droplets/particles(7).
and
THR ≤ 15 MJ.
600s
Ignitability test(8): Fs ≤ 150 mm within 60 s.
Exposure = 30 s.
D Single burning item FIGRA ≤ 750 Ws-1. Smoke production(6);
0,4MJ
test; and
and Flaming droplets/particles(7).
Ignitability test(8): Fs ≤ 150 mm within 60 s.
Exposure = 30 s.
E Ignitability test(8): Fs ≤ 150 mm within 20 s. Flaming droplets/particles(9)
Exposure = 15 s.
F Ignitability test(8): Fs > 150 mm within 20 s.
Exposure = 15 s.
(1) For homogeneous products and substantial components of non-homogeneous products.
(2) For any external non-substantial component of non-homogeneous products.
(3) Alternatively, any external non-substantial component having a PCS ≤ 2,0 MJm-2, provided that the product satisfies the
following criteria of Single burning item test: FIGRA ≤ 20 Ws-1; and
LFS < edge of specimen; and
THR ≤ 4,0 MJ; and
600s
s1; and
d0.
(4) For any internal non-substantial component of non-homogeneous products.
(5) For the product as a whole.
(6) s1 = SMOGRA ≤ 30 m2s-2and TSP ≤ 50 m2;
600s
s2 = SMOGRA ≤ 180 m2s-2and TSP ≤ 200 m2;
600s
s3 = not s1 or s2.
(7) d0 = no flaming droplets/particles in Single burning item test within 600 s;
d1 = no flaming droplets/particles persisting longer than 10 s in Single burning item test within 600 s;
d2 = not d0 or d1;
Ignition of the paper in Ignitability test results in a d2 classification.
(8) Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
(9) No ignition of the paper = no additional classification;
Ignition of the paper = d2 classification.
ELI: http://data.europa.eu/eli/reg_del/2026/331/oj 5/10EN
OJ L, 21.4.2026
2. Floorings
Table 2
Class Test method(s) Classification criteria Additional classification
A1 Non-combustibility ΔΤ ≤ 30 °C;
FL
test(1); and
and Δm ≤ 50 %;
and
t = 0 (that is to say, no sustained
f
flaming).
Heat of combustion PCS ≤ 2,0 MJkg-1(1);
test. and
PCS ≤ 2,0 MJkg-1(2);
and
PCS ≤ 1,4 MJm-2(3);
and
PCS ≤ 2,0 MJkg-1(4).
A2 Non-combustibility ΔΤ ≤ 50 °C;
FL
test(1); and
or Δm ≤ 50 %;
and
t ≤ 20 s.
f
Heat of combustion PCS ≤ 3,0 MJkg-1(1);
test; and
and PCS ≤ 4,0 MJm-2(2);
and
PCS ≤ 4,0 MJm-2(3);
and
PCS ≤ 3,0 MJkg-1(4).
Determination of the Critical flux(6)≥ 8,0 kWm-2. Smoke production(7).
burning behaviour
using a radiant heat
source test(5).
B Determination of the Critical flux(6)≥ 8,0 kWm-2. Smoke production(7).
FL
burning behaviour
using a radiant heat
source test(5);
and
Ignitability test(8): Fs ≤ 150 mm within 20 s.
Exposure = 15 s.
C Determination of the Critical flux(6)≥ 4,5 kWm-2. Smoke production(7).
FL
burning behaviour
using a radiant heat
source test(5);
and
Ignitability test(8): Fs ≤ 150 mm within 20 s.
Exposure = 15 s.
6/10 ELI: http://data.europa.eu/eli/reg_del/2026/331/ojEN
OJ L, 21.4.2026
Class Test method(s) Classification criteria Additional classification
D Determination of the Critical flux(6)≥ 3,0 kWm-2. Smoke production(7).
FL
burning behaviour
using a radiant heat
source test(5);
and
Ignitability test(8): Fs ≤ 150 mm within 20 s.
Exposure = 15 s.
E Ignitability test(8): Fs ≤ 150 mm within 20 s.
FL
Exposure = 15 s.
F Ignitability test(8): Fs > 150 mm within 20 s.
FL
Exposure = 15 s.
(1) For homogeneous products and substantial components of non-homogeneous products.
(2) For any external non-substantial component of non-homogeneous products.
(3) For any internal non-substantial component of non-homogeneous products.
(4) For the product as a whole.
(5) Test duration = 30 minutes.
(6) Critical flux is defined as the radiant flux at which the flame extinguishes or the radiant flux after a test period of 30 minutes,
whichever is the lower (i.e. the flux corresponding with the furthest extent of spread of flame).
(7) s1 = smoke ≤ 750 %.min;
s2 = not s1.
(8) Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
3. Linear pipe insulation products
Table 3
Class Test method(s) Classification criteria Additional classification
A1 Non-combustibility ΔΤ ≤ 30 °C;
L
test(1); and
and Δm ≤ 50 %;
and
t = 0 (that is to say, no sustained
f
flaming).
Heat of combustion PCS ≤ 2,0 MJkg-1(1);
test. and
PCS ≤ 2,0 MJkg-1(2);
and
PCS ≤ 1,4 MJm-2(3);
and
PCS ≤ 2,0 MJkg-1(4).
A2 Non-combustibility ΔΤ ≤ 50 °C;
L
test(1); and
or Δm ≤ 50 %;
and
t ≤ 20 s.
f
ELI: http://data.europa.eu/eli/reg_del/2026/331/oj 7/10EN
OJ L, 21.4.2026
Class Test method(s) Classification criteria Additional classification
Heat of combustion PCS ≤ 3,0 MJkg-1(1);
test; and
and PCS ≤ 4,0 MJm-2(2);
and
PCS ≤ 4,0 MJm-2(3);
and
PCS ≤ 3,0 MJkg-1(4).
Single burning item test. FIGRA ≤ 270 Ws-1; Smoke production(5);
0,2MJ
and and
LFS < edge of specimen; Flaming droplets/particles(6).
and
THR ≤ 7,5 MJ.
600s
B Single burning item FIGRA ≤ 270 Ws-1; Smoke production(5);
L 0,2MJ
test; and and
and LFS < edge of specimen; Flaming droplets/particles(6).
and
THR ≤ 7,5 MJ.
600s
Ignitability test(7): Fs ≤ 150 mm within 60 s.
Exposure = 30 s.
C Single burning item FIGRA ≤ 460 Ws-1; Smoke production(5);
L 0,2MJ
test; and and
and LFS < edge of specimen; Flaming droplets/particles(6).
and
THR ≤ 15 MJ.
600s
Ignitability test(7): Fs ≤ 150 mm within 60 s.
Exposure = 30 s.
D Single burning item FIGRA ≤ 2 100 Ws-1; Smoke production(5);
L 0,4MJ
test; and and
and THR ≤ 100 MJ. Flaming droplets/particles(6).
600s
Ignitability test(7): Fs ≤ 150 mm within 60 s.
Exposure = 30 s.
E Ignitability test(7): Fs ≤ 150 mm within 20 s. Flaming droplets/particles(8).
L
Exposure = 15 s.
F Ignitability test(7): Fs > 150 mm within 20 s.
L
Exposure = 15 s.
(1) For homogeneous products and substantial components of non-homogeneous products.
(2) For any external non-substantial component of non-homogeneous products.
(3) For any internal non-substantial component of non-homogeneous products.
(4) For the product as a whole.
(5) s1 = SMOGRA ≤ 105 m2s-2and TSP ≤ 250 m2;
600s
s2 = SMOGRA ≤ 580 m2s-2and TSP ≤ 1 600 m2;
600s
s3 = not s1 or s2.
(6) d0 = no flaming droplets/particles in Single burning item test within 600 s;
d1 = no flaming droplets/particles persisting longer than 10 s in Single burning item test within 600 s;
d2 = not d0 or d1;
Ignition of the paper in Ignitability test results in a d2 classification.
(7) Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
(8) No ignition of the paper = no additional classification;
Ignition of the paper = d2 classification.
8/10 ELI: http://data.europa.eu/eli/reg_del/2026/331/ojEN
OJ L, 21.4.2026
4. Electric cables
Table 4
Class Test method(s) Classification criteria Additional classification
A Heat of combustion PCS ≤ 2,0 MJkg-1(1).
ca
test.
B1 Burning behaviour and FS ≤ 1,75 m; Smoke production(2)(3);
ca
smoke production of and and
bunched cable test THR ≤ 10 MJ Flaming droplets/particles(4);
1200s
(30 kW flame source); and and
and Peak HRR ≤ 20 kW Acidity (pH and conductivity)(5).
and
FIGRA ≤ 120 Ws-1.
Vertical flame spread of H ≤ 425 mm.
single cable test.
B2 Burning behaviour and FS ≤ 1,5 m; Smoke production(2)(6);
ca
smoke production of and and
bunched cable test THR ≤ 15 MJ Flaming droplets/particles(4);
1200s
(20,5 kW flame source); and and
and Peak HRR ≤ 30 kW Acidity (pH and conductivity)(5).
and
FIGRA ≤ 150 Ws-1.
Vertical flame spread of H ≤ 425 mm.
single cable test.
C Burning behaviour and FS ≤ 2,0 m; Smoke production(2)(6);
ca
smoke production of and and
bunched cable test THR ≤ 30 MJ; Flaming droplets/particles(4);
1200s
(20,5 kW flame source); and and
and Peak HRR ≤ 60 kW; Acidity (pH and conductivity)(5).
and
FIGRA ≤ 300 Ws-1.
Vertical flame spread of H ≤ 425 mm.
single cable test.
D Burning behaviour and THR ≤ 70 MJ; Smoke production(2)(6);
ca 1200s
smoke production of and and
bunched cable test Peak HRR ≤ 400 kW; Flaming droplets/particles(4);
(20,5 kW flame source); and and
and FIGRA ≤ 1 300 Ws-1. Acidity (pH and conductivity)(5).
Vertical flame spread of H ≤ 425 mm.
single cable test.
E Vertical flame spread of H ≤ 425 mm.
ca
single cable test.
ELI: http://data.europa.eu/eli/reg_del/2026/331/oj 9/10EN
OJ L, 21.4.2026
Class Test method(s) Classification criteria Additional classification
F Vertical flame spread of H > 425 mm.
ca
single cable test.
(1) For the product as a whole, excluding metallic materials, and for any external component (that is to say, sheath) of the product.
(2) s1 = TSP ≤ 50 m2andPeak SPR ≤ 0,25 m2/s;
1200
s1a = s1 and transmittance in accordance with Smoke production of burning cable test ≥ 80 %;
s1b = s1 and transmittance in accordance with Smoke production of burning cable test ≥ 60 % < 80 %;
s2 = TSP ≤ 400 m2and Peak SPR ≤ 1,5 m2/s;
1200
s3 = not s1 or s2.
(3) The smoke class declared for class B1 cables must originate from the Burning behaviour and smoke production of bunched
ca
cable test (30 kW flame source).
(4) d0 = no flaming droplets/particles within 1 200 s;
d1 = no flaming droplets/particles persisting longer than 10 s within 1 200 s;
d2 = not d0 or d1.
(5) Acidity of gases produced by burning cables test:
a1 = conductivity < 2,5 μS/mm and pH > 4,3;
a2 = conductivity < 10 μS/mm and pH > 4,3;
a3 = not a1 or a2.
(6) The smoke class declared for class B2 , C , D cables must originate from the Burning behaviour and smoke production of
ca ca ca
bunched cable test (20,5 kW flame source).
10/10 ELI: http://data.europa.eu/eli/reg_del/2026/331/oj